Key Features
- 4 relay digital outputs: Type of digital output: Relays; Number of digital outputs: 4.
- Supply and diagnostics: Supply voltage rated value (DC): 24 V; diagnostics function: Yes; monitoring the supply voltage: Yes.
- SIPLUS extreme configuration: Conformal coating, -40…+70 °C, OT4 with ST1/2 (+85 °C for 10 minutes), and module diagnostics for supply voltage.
- Connection and base unit fit: Suitable for BU type B0 or B1; 2-wire connection for BU type B1; 3-wire connection for BU type B0.
Technical Summary
| Product type designation | RQ 4×120 VDC … 230 VAC/5 A NO ST |
|---|---|
| Based on | 6ES7132-6HD01-0BB1 |
| Number of digital outputs | 4 |
| Type of digital output | Relays |
| Rated value (DC) | 24 V |
| Permissible range, lower limit (DC) | 19.2 V |
| Permissible range, upper limit (DC) | 28.8 V |
| Outputs, address space | 1 byte |
| Output voltage, rated value (AC) | 230 V |
| Current per channel, max. | 5 A; > +60 °C max. continuous current per relay 3 A |
| Current per module, max. | 20 A |
| Diagnostic alarm | Yes |
| Monitoring the supply voltage | Yes |
Applications
- Switching four relay outputs: For switching four relay outputs in a digital output task.
- Redundant load control: For parallel switching of two outputs for redundant control of a load.
Frequently Asked Questions
What is the exact Siemens order number and product type for 6AG2132-6HD01-4BB1?
The exact order number is 6AG2132-6HD01-4BB1, and the product type designation is RQ 4×120 VDC … 230 VAC/5 A NO ST.
How many relay outputs does 6AG2132-6HD01-4BB1 have?
It has 4 digital outputs and 4 relay outputs.
What supply voltage does this SIPLUS ET 200SP module use?
The rated supply voltage (DC) is 24 V, with a permissible range of 19.2 V to 28.8 V.
Which BaseUnits can be used with 6AG2132-6HD01-4BB1?
Usable BaseUnits are BU type B0 and BU type B1.