Key Features
- PROFINET IO device interface module: Interface module for ET 200MP electronic modules.
- Integrated 2-port switch: 2 ports with RJ 45 (Ethernet).
- Operating range with conformal coating: -40…+70 °C with conformal coating.
- Shared device and redundancy functions: RJ45 shared device, MRP, and shared device support.
- Diagnostics and identification data: I&M0 to I&M3, status indicator, alarms, and diagnostics function.
Technical Summary
| Product type designation | IM 155-5 PN ST |
|---|---|
| Based on | 6ES7155-5AA01-0AB0 |
| Product function | I&M data: Yes; I&M0 to I&M3 |
| Firmware update | FW update possible: Yes |
| Supply voltage, rated value (DC) | 24 V |
| Supply voltage, permissible range | 19.2 V to 28.8 V |
| Input current, rated value | 0.2 A |
| Input current, max. | 1.2 A |
| Power consumption from the backplane bus | 2.3 W |
| Modules per rack, max. | 30; I/O modules |
| Number of PROFINET interfaces | 1; 2 ports (switch) |
| Interface types | RJ 45 (Ethernet): Yes |
| Transmission procedure | PROFINET with 100 Mbit/s full duplex (100BASE-TX) |
| Protocols | PROFINET IO device: Yes |
| Protocols 2 | Open IE communication: Yes |
| Protocols 3 | PROFIsafe: Yes |
| Short circuit protection | Yes |
| Reverse polarity protection | Yes |
| Mains/voltage failure stored energy time | 10 ms |
Applications
- PROFINET IO device integration: Connection of ET 200MP electronic modules to a PROFINET IO device interface.
- Open IE communication: Communication over Open IE with TCP/IP, SNMP, and LLDP.
- Media redundancy in PROFINET networks: Use as a PROFINET MRP client with shared device support.
Frequently Asked Questions
What is Siemens 6AG1155-5AA01-7AB0?
It is a SIPLUS ET 200MP IM155-5 PN ST interface module based on 6ES7155-5AA01-0AB0.
What PROFINET interface does this module provide?
It has 1 PROFINET interface with 2 ports and an integrated switch, using RJ 45 (Ethernet).
What are the power supply requirements for 6AG1155-5AA01-7AB0?
Rated supply voltage is 24 V DC, with a permissible range of 19.2 V to 28.8 V.
What are the key communication functions of this IM 155-5 PN ST?
It supports PROFINET IO device, Open IE communication, shared device, MRP, and PROFIsafe.
What identification and diagnostics data are available?
It supports I&M0 to I&M3 and provides status indicator, alarms, diagnostics function, and LED indicators.