Key Features
- 4 relay outputs: Relay module with 4 digital outputs.
- 24 V DC supply: Rated value (DC): 24 V; permissible range: 19.2 V to 28.8 V.
- Conformal coating and temperature range: Conformal coating with -40…+70 °C operating range.
- BU type support: Usable BaseUnits: BU type B0, B1.
- Diagnostics and redundancy: Diagnostics function: Yes; redundancy capability: Yes.
Technical Summary
| Product type designation | RQ 4×120 VDC … 230 VAC/5 A NO ST |
|---|---|
| Based on | 6ES7132-6HD01-0BB1 |
| Usable BaseUnits | BU type B0, B1 |
| I&M data | Yes; I&M0 to I&M3 |
| Redundancy capability | Yes |
| Rated value (DC) | 24 V |
| Permissible range, lower limit (DC) | 19.2 V |
| Permissible range, upper limit (DC) | 28.8 V |
| Number of digital outputs | 4 |
| Type of digital output | Relays |
| Current per channel, max. | 5 A; > +60 °C max. continuous current per relay 3 A |
| Rated switching voltage (AC) | 24V AC to 230V AC |
Applications
- Digital output switching: Switching 4 relay outputs for digital output control.
- Monitoring and signaling with diagnostics: Using the diagnostics function, diagnostic alarm, and status LEDs for module and channel monitoring.
- Load switching across AC and DC ratings: Switching loads with rated switching voltage of 24 V DC to 120 V DC and 24V AC to 230V AC.
Frequently Asked Questions
What is Siemens 6AG1132-6HD01-7BB1?
It is a SIPLUS ET 200SP RQ 4x relay output module.
How many digital outputs does 6AG1132-6HD01-7BB1 have?
It has 4 digital outputs.
What supply voltage does 6AG1132-6HD01-7BB1 use?
Rated value (DC): 24 V; permissible range: 19.2 V to 28.8 V.
Which BaseUnits can be used with 6AG1132-6HD01-7BB1?
Usable BaseUnits: BU type B0, B1.
What should be confirmed before ordering this Siemens module?
Confirm the exact model, requested quantity, destination, stock, and dispatch conditions.