Key Features
- SIPLUS NET OLM G12-1300 V4.0: Product designation: OLM/G12-1300 V4.0.
- Interface configuration: 1 RS-485 and 2 glass fiber optic cable interfaces, with 4 BFOC sockets.
- Transmission support: Transfer rate / with PROFIBUS: 9.6 kbit/s … 12 Mbit/s.
- Long-distance fiber link: 1300 Nm shaft length for large distances.
- Installation and enclosure: 35 mm DIN-rail mounting, wall mounting, and IP40 protection class.
- Operating conditions: Operating temperature: -25 … +60 °C.
Technical Summary
| Product type designation | OLM/G12-1300 V4.0 |
|---|---|
| Product brand name | SIPLUS |
| Transfer rate / with PROFIBUS | 9.6 kbit/s … 12 Mbit/s |
| Transfer rate / with PROFIBUS PA | 45.45 kbit/s |
| Number of optical interfaces / for fiber optic cable | 2 |
| Design of the optical interface / for fiber optic cable | BFOC port |
| Type of electrical connection / for network components or terminal equipment | 9-pin Sub-D socket |
| Type of electrical connection / for power supply and signaling contact | 5-pole terminal block |
| Supply voltage / at DC / rated value | 24 V |
| Supply voltage / at DC | 18.8 … 28.8 V |
| Ambient temperature / during operation | -25 … +60 °C |
| Protection class IP | IP40 |
Applications
- PROFIBUS fiber link integration: Connection of PROFIBUS networks over glass fiber optic cable interfaces.
- Signaling contact connection: Connection of the signaling contact through the 5-pole terminal block.
Frequently Asked Questions
What is the exact Siemens model of this OLM module?
The exact model is 6AG1503-3CC00-2AA0.
What interfaces are included on 6AG1503-3CC00-2AA0?
It has 1 RS-485 interface and 2 glass fiber optic cable interfaces with 4 BFOC sockets.
What PROFIBUS transfer rates does this module support?
PROFIBUS transfer rate is 9.6 kbit/s … 12 Mbit/s, and PROFIBUS PA transfer rate is 45.45 kbit/s.
What power supply is required for this SIPLUS OLM?
The rated supply voltage is 24 V DC, and the supply voltage range is 18.8 … 28.8 V.