Key Features
- IM 155-6 PN/2 HF: Product type designation: IM 155-6 PN/2 HF.
- PROFINET 2-port interface: 1 PROFINET interface with 2 ports (switch) and integrated switch.
- Module capacity: Max. 64 I/O modules and 16 ET 200AL modules.
- Redundancy and service features: S2 redundancy, multi-hotswap, isochronous mode, and PROFINET MRP client support.
- BusAdapter connection: 1 slot for BusAdapter with RJ 45 (Ethernet) options.
Technical Summary
| Product type designation | IM 155-6 PN/2 HF |
|---|---|
| Firmware version | V4.2 |
| FW update possible | Yes |
| Supply voltage, rated value (DC) | 24 V |
| Supply voltage, permissible range, lower limit (DC) | 19.2 V |
| Supply voltage, permissible range, upper limit (DC) | 28.8 V |
| Current consumption, max. | 700 mA |
| Power loss, typ. | 2.4 W |
| Number of PROFINET interfaces | 1; 2 ports (switch) |
| BusAdapter (PROFINET) | Yes; BA 2x RJ45, BA 2x FC, BA 2x M12, BA 2x SCRJ, BA SCRJ/RJ45, BA SCRJ/FC, BA 2x LC, BA LC/RJ45, BA LC/FC |
| PROFINET IO device | Yes |
| PROFIsafe | Yes |
| PROFINET system redundancy (S2) | Yes; NAP S2 |
| Isochronous mode | Yes |
| Number of operable ET 200SP modules, max. | 64 |
| Quantity of operable ET 200AL modules, max. | 16 |
| Isolation tested with | 707 V DC (type test) |
| Connection display LINK TX/RX | Yes; 2x green link LEDs on BusAdapter |
| Product lifecycle | Active Product |
Applications
- PROFINET network integration: Connects the SIMATIC ET 200SP station to a PROFINET network.
- I/O station expansion: Supports a station with up to 64 I/O modules and 16 ET 200AL modules.
Frequently Asked Questions
What is the exact Siemens model of this ET 200SP interface module?
The exact model is 6ES7155-6AU01-0CN0 with product type designation IM 155-6 PN/2 HF.
What PROFINET interface details does this module have?
It has 1 PROFINET interface with 2 ports (switch) and an integrated switch.
What is the supported supply voltage for this module?
Rated value is 24 V DC, with a permissible range from 19.2 V DC to 28.8 V DC.
How many modules can this station support?
It supports up to 64 I/O modules and 16 ET 200AL modules.
What should be confirmed before ordering for stock and dispatch?
Confirm the exact order number, requested quantity, and destination before requesting stock and dispatch conditions.