Key Features
- Digital output module: SIMATIC ET 200SP digital output module with DQ 4x 24VDC/2A Standard configuration.
- BU and coding details: Suitable for BU type A0 and equipped with color code CC02.
- Diagnostics and protection: Module diagnostics, diagnostics function, diagnostic alarm, supply voltage monitoring, and short-circuit protection are supported.
- Output and supply ratings: Rated supply voltage is 24 V DC, with 4 digital outputs and 2 A per channel.
- Installation and wiring options: Supports 1-wire, 2-wire, 3-wire, and 4-wire connection variants with the listed BaseUnit arrangements.
Technical Summary
| Product type designation | DQ 4×24 V DC/2 A ST |
|---|---|
| Usable BaseUnits | BU type A0 |
| Color code for module-specific color-coded label | CC02 |
| Firmware version | V1.1.5 |
| HW functional status | FS20 or higher |
| I&M data | Yes; I&M0 to I&M3 |
| Rated supply voltage (DC) | 24 V |
| Permissible supply voltage range (DC), lower limit | 19.2 V |
| Permissible supply voltage range (DC), upper limit | 28.8 V |
| Number of digital outputs | 4 |
| Type of digital output | Source output (PNP, current-sourcing) |
| Switching capacity with resistive load, max. | 2 A |
Applications
- Four-channel 24 V DC output switching: Switching four 24 V DC digital outputs with 2 A per channel.
- Load control with redundant switching: Redundant control of a load through parallel switching of two outputs.
- Output diagnostics and supply monitoring: Monitoring supply voltage, wire break, short-circuit, and module status through the diagnostics functions.
Frequently Asked Questions
What is the exact Siemens model and product type of 6ES7132-6BD20-0BA0?
It is a SIMATIC ET 200SP digital output module with product type designation DQ 4×24 V DC/2 A ST.
What are the output and supply ratings for this ET 200SP module?
The module has 4 digital outputs, a rated supply voltage of 24 V DC, and a maximum 2 A per channel.
Which BaseUnit and wiring variants are supported for 6ES7132-6BD20-0BA0?
It is suitable for BU type A0 and supports 1-wire, 2-wire, 3-wire, and 4-wire connection variants with the listed BaseUnit arrangements.
What diagnostics and protection functions are included?
It supports module diagnostics, diagnostic alarm, supply voltage monitoring, wire break monitoring, short-circuit monitoring, and electronic short-circuit protection.