Key Features
- SIMATIC DP CPU for ET200S: IM151-8 PN/DP CPU for ET200S.
- Integrated PROFINET interface: 1x PROFINET with 3 RJ45 ports and integrated switch.
- 192 KB work memory: Integrated work memory: 192 kbyte.
- MMC support: Plug-in (MMC) is supported; maximum 8 Mbyte.
- 24 V DC supply: Rated value (DC): 24 V; permissible range: 20.4 V to 28.8 V.
Technical Summary
| Product lifecycle | Product cancellation |
|---|---|
| Firmware version | V3.2 |
| HW functional status | 01 |
| Work memory | 192 kbyte |
| Rated value (DC) | 24 V |
| Permissible range, lower limit (DC) | 20.4 V |
| Permissible range, upper limit (DC) | 28.8 V |
| Interfaces/bus type | 1x PROFINET (3 RJ45 ports) |
| Transmission rate, max. | 100 Mbit/s; full duplex |
| PROFINET IO Controller | Yes; Also simultaneously with IO-Device functionality |
| Integrated switch | Yes |
| Plug-in (MMC), max. | 8 Mbyte |
Applications
- PROFINET IO integration: Use for PROFINET IO Controller communication, with simultaneous IO-Device functionality.
- Industrial Ethernet communication: Use for Open IE communication via the integrated PROFINET interface with TCP/IP, ISO on TCP, and UDP.
- PROFIBUS DP master communication: Use for PROFIBUS DP master communication with up to 32 DP devices per station.
Frequently Asked Questions
What is the exact Siemens model 6ES7151-8AB01-0AB0?
It is a SIMATIC DP IM151-8 PN/DP CPU for ET200S.
What power supply does 6ES7151-8AB01-0AB0 use?
Rated value (DC): 24 V, with a permissible range of 20.4 V to 28.8 V.
How many PROFINET ports does 6ES7151-8AB01-0AB0 have?
It has 3 RJ45 ports on the integrated PROFINET interface.
Does 6ES7151-8AB01-0AB0 support a memory card?
Yes. Plug-in (MMC) is supported, and the maximum size is 8 Mbyte.